029 2046 3345

Introducing our series of WRAS approved valves

Posted on: Friday, May 08, 2015

The L182 series are a pilot operated WRAS
approved solenoid valve, Normally closed with EPDM seals. 240v as standard with other options available upon request. Diaphragm valve, pilot operated, having full orifice.According to standards / UL and CSA UL andCSA Suitable to shut off liquid and gaseous fluids ( verify the compatibility Encapsulation material PA PET PET of fluid with material in contact ).

FEATURES
Fluid Temp - NBR -10oC to +90oC
                     FPM 0oC to 130oC
                     EPDM - 10oC to + 140oC
Opening time - 300ms - 1500ms
Closing time - 1000ms - 2000ms
Body - Brass
Sealing - NBR, FPM or EPDM
Internal components  - Brass or Stainless
Steel
Seat - Brass
Core Tube - Stainless Steel
Shading Coil - Copper

We have complimented our range of WRAS
approved valves to include the Danfoss EVSI
solenoid valve, increasing our size range from 1/2” to 2” valves.
EV220B 15–50 is a universal indirect servo-
operated 2/2-way solenoid valve. Valve body
as standard in brass, dezincification resistant
brass and stainless steel options ensures that a broad variety of application can be covered. Built-in pilot filter as standard, adjustable closing time and enclosures up to IP67 as optional extras ensures optimal performance even under critical working conditions.

 

FEATURES
For water, steam,oil, compressed air & gases
Flow range for water: 1.3 – 160 m³/h
Differential pressure: 0.3 – 16 bar
Media temperature from -30 to +140°C
Ambient temperature: Up to 80°C
Coil enclosure: Up to IP67
Thread connections: From G ½ – G 2
DN 15 – 50
Viscosity: Up to 50 cSt
Water hammer damped
Built in filter for protection of pilot system
Adjustable closing time available

Heat & Combustion Supplies

Unit E5, Southpoint Industrial Estate
Foreshore Road, Cardiff Bay, Cardiff CF10 4SP

Tel: +44 (0) 29 20 463345
Fax: +44 (0) 29 20 463346

sales@heatcombustion.co.uk
www.heatcombustion.co.uk

Disclaimer:
Please refer to manufacturers documentation for
full safety specification and correct fitting.